Brands
|
N/A
 Eagle Signal
|
Model
|
N/A
DA100
|
Type
|
N/A
Timer
|
Operating Voltage/Frequency
|
N/A
120 VAC (+10 -15%), 50/60 Hz or 120 VDC (+10 -15%) 240 VAC (+10 -15%), 50/60 Hz or 240 VDC (+10 -15%) 24 VAC, 50/60 or 24 VDC
|
Repeatability (Constant Voltage and Temperature)
|
N/A
±0.1% of setting or 25 ms, whichever is longer
|
Repeatability (Voltage and Temperature Variation)
|
N/A
Variable Voltage: ±1% of setting Variable Temperature: ±2% of setting Variable Voltage and Temperature: ±3% of setting
|
Reset Time
|
N/A
65 ms
|
Cycle Progress
|
N/A
Pilot lights during ON time and OFF time
|
Power on Response
|
N/A
30 ms maximum after line voltage applied to pins A and B
|
Power Interruption
|
N/A
Line voltage interruptions of 20 ms or less will not reset unit
|
Transient Voltage Immunity
|
N/A
Unaffected by 50 microseconds, 600 V peak transients superimposed on the line input
|
Setting Accuracy
|
N/A
Within ± 10% of maximum range
|
Operating Temperature
|
N/A
32 to 140 ºF0 to 60 ºC
|
Vibration
|
N/A
Unit function is unaffected by 2.5G sinusoidal vibration magnitude in both directions of three perpendicular mounting axes imposed from 10 to 100 Hz
|
Certification
|
N/A

|